32-Zone Control Panel

Floodline 32-Zone Control Panel

Basics
The Multi-Zone Control Panel operates the network of leak detection zones. A zone can be a single point or many metres long and the whole network is continuously monitored for leaks and continuity.

Zones are electrically isolated from each other and individually displayed so the system can accept and report any number of simultaneous or consecutive zone alarms - true multiple leak reporting - an alarm zone has no effect on the normal monitoring of its neighbours or the rest of the system.

LEDs provide clear and easy to understand status and alarm information. Output relays are provided for connection to remote alarms, BMC etc. Leak detection is shown clearly as LEAK. Sensor or cable damage or failure is shown as SYSTEM FAULT.

  • Features
  • Photos
  • Contact
  • Features/Operation
    Zone Capacity: Maximum of 32 Zones

    Function
    Water/liquid detection (other 12VDC latchable sensing devices can also be connected)

    Power: 110/230 VAC, 50Mhz, mains operated, 12VDC internal and battery back-up

    Construction: Powder coated, shielded steel enclosure

    Dimensions: H360mm x W455mm x D130mm

    Fixing: Wall/Surface mounted

    Monitoring
    LEAK - continuous water/liquid detection - each zone separately
    SYSTEM FAULT - sensor or leader cable damage, failure or disconnection

    Alarm Indicators
    Flashing LEDs for LEAK or SYSTEM FAULT (all alarms displayed separately and continuously, until corrected and restored)
    Buzzer - operates in all alarm conditions. Silence by mute/accept button

    Status Indicators
    Mains power supply
    battery operation
    internal 12VDC supply
    low battery
    alarm accept (mute)

    Function Switches
    Mute (buzzer silence/alarm accept) button
    security key-switch for output disable/reset

    Outputs
    1. LEAK in any zone - DPCO relay max 5A @ 230V
    2. SYSTEM FAULT in any zone - SPCO relay max 5A @ 230V
    3. Drop dead/power fail - SPCO relay max 5A @ 230V
    4. LEAK in each individual zone - SPCO relay max 1A @ 30VDC - optional

    All relays have "clean" volt-free contacts


  • HVAC Europe

    Postbus 2
    NL-1970 AA IJmuiden
    Telephone +31 255 52 24 20
    E-mail info@hvac.eu

  • Call me
  • Call me

    Fill your data, the day and the part of the day when you want us to call you.

  • E-mail me
  • E-mail me

    Fill your data and your question below. We will e-mail you.

Viewed products

32-Zone Control Panel